Raptors Trading & Contracting

ENERGY METERS

ENERGY METERS

An electricity meter, electric meter, electrical meter, or energy meter is a device that measures the amount of electric energy consumed by a residence, a business, or an electrically powered device.

SINGLE PHASE - DIRECT INPUT - M1DL-MID

Those energy meters used for billing should have MID Certification. Thus, the quality of the instruments is ensured having been necessary to control by a notified body that just it.
1. SINGLE-PHASE.
2. ACCURACY CL.1 (EN 62053).
3. DIRECT MEASUREMENT UP TO 50 A.
4.INTERNAL SHUNT.
5. ENERGY CONSUMPTION LED.
6.7 DIGITS ELECTRONIC COUNTER.
7.PULSE OUTPUT SO (DIN 43864).
8. 1 DIN MODULE.

TECHNICAL SPECIFICATIONS

VOLTAGE INPUT

Rated Voltage (Un)

230 V A.C.

Burden

< 8 VA, 2 W

Operating range

± 15 % Un

Frequency

50 - 60 Hz

CURRENT INPUT

Current IB (IMAX)

10 (80) A

Burden

< 3 VA

Operating range

0-100 % IMAX

Starting current (In)

< 0,4 % IB

GENERAL FEATURES

Counter type

Electromechanical

Digits

6 + 2 decimal

Nº of counters

1 (Total)

Class

1 ( EN 62053)

Operating temperature

- 20 to +55 ºC

Energy indicator

Flashing LED

Pulse weight

1000 pulses / kWh

Case material

ABS, UL94 V0

Dimensions

4 modules (70 mm)

Terminals

Sealable

Connection

With screw

Max. wire section

Phase input terminals

25 mm

Mounting

35 mm DIN rail

THREE-PHASE - DIRECT INPUT - TCIDL1

Those energy meters used for billing should have MID Certification. Thus, the quality of the instruments is ensured having been necessary to control by a notified body that just it.

1. SINGLE-PHASE.
2. ACCURACY CL.1 (EN 62053).
3. DIRECT MEASUREMENT UP TO 80 A.
4.ENERGY CONSUMPTION LED.
5.CURRENT CHECKING LED.
6.8 DIGITS ELECTRONIC COUNTER.
7.PULSE OUTPUT SO (DIN 43864).
8. 4 DIN MODULE.

TECHNICAL SPECIFICATIONS

VOLTAGE INPUT

Rated Voltage (Un)

3x230 (400) V A.C.

Burden

< 8 VA, 2 W

Operating range

± 15 % Un

Frequency

50 - 60 Hz

CURRENT INPUT

Current IB (IMAX)

10 (80) A

Burden

< 3 VA

Operating range

0-100 % IMAX

Starting current (In)

< 0,4 % IB

GENERAL FEATURES

Counter type

Electromechanical

Digits

6 + 2 decimal

Nº of counters

1 (Total)

Class

1 ( EN 62053)

Operating temperature

- 20 to +55 ºC

Energy indicator

Flashing LED

Pulse weight

1000 pulses / kWh

Case material

ABS, UL94 V0

Dimensions

4 modules (70 mm)

Terminals

Sealable

Connection

With screw

Max. wire section

Phase input terminals

25 mm

Mounting

35 mm DIN rail

THREE-PHASE - INDIRECT INPUT - TI96 - TIV96

Those energy meters used for billing should have MID Certification. Thus, the quality of the instruments is ensured having been necessary to control by a notified body that just it.

1.UNBALANCED 3-PHASE.
2.ACTIVE ENERGY OR ACTIVE ENERGY + REACTIVE ENERGY.
3. CL. 2 ACCURACY (EN 62053).
4.SELECTABLE PRIMARY CURRENT.
5.INSULATED CURRENT (INTERNAL TRANSFORMERS).
6. ENERGY CONSUMPTION LED.
7. 7 DIGITS ELECTROMECHANICAL COUNTER.
8. PULSE OUTPUT (RELAY): SO (DIN 43864).
9. 96 X 96 DIN DIMENSIONS.

TECHNICAL SPECIFICATIONS

VOLTAGE INPUT

Rated Voltage (Un)

110, 230, or 400 V C.A.

Burden

< 1 mA x U phase N

Operating range

20-120 % Un

Frequency

50 - 60 Hz

CURRENT INPUT

Current IB (IMAX)

X/1 or X/5 A

Burden

< 0,2 VA

Operating range

0-100 % IMAX

Starting current (In)

1 % IB

GENERAL FEATURES

Accuracy Class 2 (Optional)

Class 2 | Class 1

Operating temperature

- 5 to +55 ºC

Energy indicator

Flashing LED

Pulse weight

16 pulses / kWh

Case materia

Metálica+ABS, UL94 V0

Dimensions

DIN 96x96 mm

Connection

Current inputs, M4

Terminals

Pluggable

Max. wire section

2,5 mm

Terminals

Sealable

TOTALIZER TERMINALS TTI /TTIM

TTI: Totalyzer module with the microprocessor and serial output. TTIM: Totalyzer module with a microprocessor and serial output. 128 kB, LCD display, and built-in keypad.

1.8 INDEPENDENT PULSE COUNTERS.
2. INDEPENDENT COUNTER RESET.
3. PROGRAMMABLE COUNTER VALUE.
4. TTIM: 90 DAYS OF LOAD CURVE PER COUNTER.
5. RS485 SERIAL OUTPUT  PROGRAMMABLE. (ABLE TO MEASURE CLOSED CONTACT TIME IN. SECONDS, TIME, OR PULSES.

TECHNICAL SPECIFICATIONS

VOLTAGE INPUT

Rated Voltage (Un)

230 V A.C.

Burden

< 8 VA, 2 W

Operating range

± 15 % Un

Frequency

50 - 60 Hz

CURRENT INPUT

Aux. V

100, 110, 230 or 400 V C.A

Burden

4 VA

Operating range

80-120 % Un

GENERAL FEATURES

Case material

ABS, UL94 V0

Dimensions

(9 modules) 155 x 90

Terminals

Pluggable

Max. wire section

2,5 mm

Weight

0,40 kg

Operating temperature

5 to +55 ºC

Electrical safety (EN 61010)

Class 2, Category 3

MULTIFUNCTION RECORDING METERS CTMRII And CTMRIID

CTMRII and CTMRIID are static meters for a 3-phase connection. They measure active and reactive energy with classes 1 and 2. respectively. Moreover, these meters include built-in recording functions for type 2, 3, and 4 customers. They have a four-line, twenty-character display for data displaying, two buttons, one for bill closures and another for display management, LED diodes for checking active and reactive energy measurement, signal outputs using relays, and pulse emission by solid-state relays. They also have three communication interfaces, a UNE EN 62056-21 optical one, an RS232 electrical one, and an RS232 or RS485 one. The communication protocol is UNE EN 61870-5-102, which can be adapted by the System Operator.

AVAILABLE INFORMATION

Additionally, the meter has the following information
1.Phase voltage and line voltage.
2.Currents.
3. Active, reactive, and apparent power, global and per phase phi cos.
4. Frequency.
5. Information about software updates.
6. Information about special actions (reset to zero, transformation ratio, and burden curve periods).
7.Backup of the main values.

GENERAL FEATURES

DisplayCounter type

4x20 LCD alphanumeric characters

Communication

Protocol

published by System Operator

Optical

According to UNE EN 61107, programmable baud rate up to 9600 bauds, parity programmable

Local port

RS232 direct or via modem, programmable, speed up to 115200 bauds, parity programmable.

Operating reserve

10 years.

Buttons

1 sealable for manual reset to zero

1 for display management

Battery

polarized housing for easy change over

Dimensions

1 module (17,5 mm)